Figure 4-13: CAN and Pull-Chain wiring for parallel UPS without MOBs

NOTE
NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open)
position. If MOB contacts have pigtail leads, use the same wire gauge to connect to the UPS
and use the correct crimp connections for the wire gauge. External CAN connections between
UPS cabinets require shielded twisted pair wire. Use twisted pair wiring between the UPS and
MOB AUX contacts. Always confirm contact operation prior to wiring.
52
30-200 kW
P-164000249
User's and Installation Guide
Revision 2