Rack Compatibility
TABLE 2-1
Item
Clearance depth in front of front
mounting plane
Clearance depth behind front
mounting plane
Clearance width between front
and rear mounting planes
Caution – Always load equipment into a rack from the bottom up so that it will not
become top-heavy and tip over. Deploy your rack's anti-tip bar to prevent the rack
from tipping during equipment installation.
Caution – Ensure that the temperature in the rack does not exceed the server's
maximum ambient rated temperatures. Consider the total airflow requirements of all
equipment installed in the rack to ensure that the equipment is operated within its
specified temperature range.
Disassembling Slide-Rails
Do one of the following procedures before installation:
"Disassembling Bolt-On Slide-Rails" on page 11
■
"Disassembling Tool-less Slide-Rails" on page 12
■
Disassembling Bolt-On Slide-Rails
To remove the mounting-brackets from the bolt-on slide-rail assemblies:
1. Unpack the slide-rails.
2. Locate the slide-rail lock at the front of one of the slide-rail assemblies, as
shown in
FIGURE 2-1
Chapter 2
Requirement
Distance to front cabinet door is at least 25.4
mm (1 inch).
Distance to rear cabinet door is at least 800
mm (31.5 inches) with the cable management
arm, or 700 mm (27.5 inches), without the
cable management arm.
Distance between structural supports and
cable troughs is at least 456 mm (18 inches).
.
Installing the Sun Fire X4450 Server Into a Rack with Slide-Rails
11