Ups Maintenance; Ups And Battery Care; Storing The Ups And Batteries - Avaya S9RM Installation And Operator's Manual

Table of Contents

Advertisement

Chapter 7

UPS and Battery Care

Storing the UPS and Batteries

Avaya

UPS Maintenance

This section explains how to:
S
Care for the UPS and batteries
S
Replace the batteries
S
Test new batteries
S
Recycle used batteries or UPS
For the best preventive maintenance, keep the area around the UPS
clean and dust-free. If the atmosphere is very dusty, clean the outside of
the system with a vacuum cleaner.
For full battery life, keep the UPS at an ambient temperature of
25°C (77°F).
NOTE If the UPS requires any type of transportation, verify that the UPS is unplugged and
turned off and then disconnect the UPS internal battery connector using the steps in
"Connecting the UPS Internal Battery" on page 19 in reverse order.
NOTE The batteries in the UPS are rated for a 3–5 year service life. The length of service
life varies, depending on the frequency of usage and ambient temperature. Batteries used
beyond expected service life will often have severely reduced runtimes. Replace batteries at
least every 5 years to keep units running at peak efficiency.
If you store the UPS for a long period, recharge the battery every
12 months by plugging the UPS into a power outlet. The batteries
charge to 80% capacity in approximately 2 hours. However, it is
recommended that the batteries charge for 36 hours after long-term
storage.
Check the battery recharge date on the shipping carton label. If the date
has expired and the batteries were never recharged, do not use the
UPS. Contact your Avaya service representative.
t
S9RM UPS Site Preparation, Installation and Operator's Manual
S
49
05147387 Rev C