Fault Codes
Error Source
Secondary Boom Switch
Timeout
Secondary Boom Switches
Intermittence Fault (LSS1RS
Fault)
Jib Angle Sensor
Operational (RSJ1AO)
SCON Tilt Sensor
LSS1RO Fault
218
Error Type
Too much time
Inhibit Secondary Boom Extend if the
fault occurs.
has elapsed from
when LSS1RO is
released and
LSS1RS is
released on
extend and
LSS1RS is
engged and
LSS1RO is
engaged. Or the
joystick was
engaged three
times in the
interval.
Either LSS1RS or
Inhibit Secondary Boom Down until the
LSS1RO have
fault is cleared.
changed state
without a
secondary boom
extend/retract
command or they
have changed
state when the
secondary boom
is not fully raised.
Value at 5.0 V
Limited Speed and Direction frozen at
zero and neutral, Alarm sounds
Value Too High
Value Too Low
Value at 0 V
Calibration check
Display X direction and Y direction not
calibrated
LSS1RO did not
Inhibit secondary boom extend and
switch within a
sound an audible warning
specified time
after the
secondary boom
was raised
Effects
ZX-135/70
August 2014
Recovery Actions
If the fault occurs on extend, retract
boom until LSS1RO is engaged and
try again. Check LSS1RS and
LSS1RO for physical damage and
proper operation.
Check switch for proper operation or
damage. Use TCON display menu or
laptop with WebGPI to clear faults.
Power up controller with problem
corrected.
Re-power after entering tilt x axis and
y axis matrix information
Check switch for proper operation or
damage. Use TCON display menu or
laptop with WebGPI to clear faults.
Part No. 218700