Indicates than an incorrect result has occurred after performing a series of steps. PCON - Platform controls Note: These installation instructions only apply to the Genie models listed on the front cover, as required by Service Advisory 140007. Software Update Part No. 1258800...
Page 3
Introduction Machine Software Version Components of Kit 1258799 Update Requirements Flash drive, Z135/ZX135, V3.06 Genie part number 1258799 Machines equipped with platform overload Qty. 1 protection and an operating system with a software version less than 3.00 must install Includes: load sense upgrade kit 1258801.
Page 4
Instructions Rev A Introduction If you have any further questions regarding these instructions or need assistance, please contact Genie Product Support at one of the following telephone numbers: United States: 800-536-1800 Canada: 425-881-1800 Europe: 0044 1476 584 333 France 0033 237 260 986...
Application Software Installation. Read and record the scroll message on the Insert the thumb drive (Genie part display (example: VER 2_10 is version 2.10). number 1258799) into the computer or laptop. Push in the red Emergency Stop button.
Page 6
Instructions Rev A Procedure Select Yes on the License Agreement On the Setup Type screen select Typical, screen. then select Next. Note: After pressing Next you will see a series of On the Choose Destination screen record the file names flash across the screen. When the default destination folder and select Next.
Page 7
COM settings. The COM port settings can vary between computers. Click on the Application icon. Connect the SCON Tee-Harness (Genie part number 107647) between the gray connector and the SCON. Connect the laptop DB9 cable to the Tee-Harness.
Page 8
Instructions Rev A Procedure Select Check Parameters. 13 Select File type: Kernel. Select Tilt Sensors Params. Read and record 14 Click on the Search button and locate the Tilt Angle Matrix Gains parameters. application software S0829306.HEX. 10 Click on the Disconnect icon. 11 Click on the Connect icon.
Page 9
Rev A Instructions Procedure 18 When the Kernel file is at 100%, cycle the 15 Select S0829306.HEX, and then click on power off, then back on at the red Emergency Open. Stop Button at the TCON. 19 Click on the Exit button, then the Application icon.
Page 10
Instructions Rev A Procedure 21 When prompted, select Level 2, enter SG81355 for the password and select Accept.Select Check Parameters. 22 Select Tilt Sensors Params. Enter the parameters that were recorded in step 9. Note: The numbers must be entered accurately.
Page 11
Rev A Instructions Procedure TCON Software Update Open WebGPI™ and click on the Connect icon. Note: Before installation, go to your computers Control Panel and increase your computers time out period to more than 30 minutes. Open the ground control box and set the fasteners aside.
Page 12
Instructions Rev A Procedure Click on the Search button and locate Click on the Download button. application software S0827306. HEX. Note: This download can take 10 to 30 minutes depending on the speed of your serial connection. If your computer times out you will have to repeat the TCON Software Update.
Page 13
Rev A Instructions Procedure 10 Cycle the power off, then back on at the red 13 When prompted, select Level 2, enter Emergency Stop Button at the TCON. SG81355 for the password and select Accept. 11 Click on the Application icon. 14 Push in the red Emergency Stop Button and disconnect the DB9 cable from the TCON PCB.
Page 14
Instructions Rev A Procedure PCON Software Update Open WebGPI™ and click on the Connect icon. Open the platform control box and set the fasteners aside. Connect the computer DB9 cable to the PCON PCB. Note: The current application software file will be shown at the top of the screen.
Page 15
Rev A Instructions Procedure Select File Type: Kernel. Select S0828306.HEX, and then click on Open. Click on the Search button and locate application software S0828306.HEX. Click on the Force download button. Cycle the power off, then back on at the red Emergency Stop Button at the TCON.
Page 16
Instructions Rev A Procedure 10 Click on the Download button. 13 Select Set All Defaults. Select Ok. 11 When the Kernel file is at 100%, cycle the power off, then back on at the red Emergency 14 When prompted, select Level 2, enter Stop Button at the PCON.