CHAPTER 3 Precautions Pertaining to Delivery and Installation

(2) Through-floor anchoring

Special leveling feet must be prepared separately to anchor a unit by using this
anchoring method.
Each leveling foot of a unit must be replaced with F6-DA6G when it is bolted
from the underside of the floor.
3-4
Unit
(Floor)
Figure 3.2 Earthquake-proofing construction method
(through-floor anchoring)
Leveling foot (F6-DA6G)
Bolt
U41631-J-Z816-5-76