Input Power Supply Unit Connections; Table 2.3 Ac Cable Specifications For The Primequest 580A/540A/580/540/480/440 Main Unit - Fujitsu PRIMEQUEST 580A Installation Planning Manual

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

CHAPTER 2 Connection Reference
2.4

Input Power Supply Unit Connections

The following table lists the connection specifications for the input power supply unit.
PRIMEQUEST 580A/540A/580/540/480/440 main unit (Section
Cables between PCI_Box and ACS in the Extended I/O Cabinet (Section
Cables between ACS in the Extended I/O Cabinet and power distribution board
(Section
2.4.1
PRIMEQUEST 580A/540A/580/540/480/440 main unit
Table 2.3
PRIMEQUEST 580A/540A/580/540/480/440 main unit.
Table 2.3 AC cable specifications for the PRIMEQUEST 580A/540A/580/540/
Destination
JAPAN
Outside Japan
(general)
Europe
Note:
Use the supplied accessory AC cable to connect the main unit. Do not use
the accessory AC cable for other products.
2-38
2.4.3)
lists the specifications for connecting the input power supply unit to the
Two-prong hook-type plug with
grounding electrode (250V30A)
NEMA standard name: L6-30P
NEMA L6-30P
IEC60309 (32A)
480/440 main unit
Plug type
2.4.1)
Remarks
Power-receiving outlets must be
available.
Two-prong hook-type receptacle
with grounding electrode
(250V30A)
NEMA L6-30R
Embedded type: 3320-L6
(American Denki)
Exposed type: 3321-L6
(American Denki)
NEMA L6-30R
(only for North America)
30A-220 VAC
IEC60309 (32A)
U41631-J-Z816-5-76
2.4.2)

Advertisement

Table of Contents
loading

Table of Contents