Fujitsu PRIMEQUEST 580A Installation Planning Manual page 46

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

CHAPTER 1 Installation Reference
Power supply
Input voltage tolerance and No. of phases
Frequency and tolerance
Maximum
power
consumption/
apparent
power (*8)
Power factor
Inrush current [A] [Inrush duration] (*9)
Leakage current [mA] (*9)
CB/breaker capacity [A]
*1:
This value does not include any projection.
*2:
Value for the case with the maximum number of optional units allowed
installed.
The weight of the unit based on the equipment configuration can be
calculated from the following formula:
When 32-GB memory is mounted, the formula is as follows:
*3:
When up to 2 TB-memory is mounted, the maximum heat dissipation is
44,600 KJ/h.
1-18
Item
Operating
Not operating Five SBs or five IO
Unit weight = 492 + (12 x A) + (15 x B) + (1 x C) + (10 x D)
Unit weight = 492 + (13 x A) + (15 x B) + (1 x C) + (10 x D)
A = Number of SBs mounted:
B = Number of IOUs mounted:
C = Number of GSWBs or GTHBs mounted:
D = Number of Additional Power Supply Units mounted:
Five SBs or five IO
Units or more
Four SBs or less and
four IO Units or less
Units or more
Four SBs or less and
four IO Units or less
From a minimum of one to a
maximum of eight
From a minimum of one to a
maximum of eight
From a minimum of zero to a
maximum of two
From a minimum of zero to a
maximum of one
Value
200 to 240 VAC ± 10 %
50/60 Hz +2/-4 Hz
10,900 W/
11,000 VA
6,300 W/
6,400 VA
300 VA
300 VA
0.9 or more
100 or less
3.5 or less
20
U41631-J-Z816-5-76