Fujitsu PRIMEQUEST 580A Installation Planning Manual page 56

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

CHAPTER 1 Installation Reference
Power supply
Input voltage tolerance and No. of phases
Frequency and tolerance
Maximum
power
consumption/
apparent
power
Power factor
Inrush current [A] [Inrush duration] (*7)
Leakage current [mA] (*7)
CB/breaker capacity [A]
*1:
This value does not include any projection.
*2:
Value for the case the maximum allowable number of optional units is
mounted.
The weight of the unit based on the equipment configuration can be
calculated from the following formula:
*3:
There must be no condensation.
1-28
Item
Operating
Not operating Five SBs or five IO
Unit weight = 290 + (10 x J)
J = Number of Additional Power Supply Units mounted:
Five SBs or five IO
Units or more
Four SBs or less and
four IO Units or less
Units or more
Four SBs or less and
four IO Units or less
From a minimum of zero to a
maximum of one
Value
200 to 240 VAC ± 10 %
50/60 Hz +2/-4 Hz
10,900 W/11,000 VA
(For PRIMEQUEST
580A/580)
10,600 W/10,700 VA
(For PRIMEQUEST
480)
6,490 W/6,630 VA
(For PRIMEQUEST
580A/580)
5,890 W/6,000 VA (For
PRIMEQUEST 480)
300 VA
300 VA
0.9 or more
100 or less
3.5 or less
20
U41631-J-Z816-5-76