2.5 AC Cable Connection under a Free-Access Floor (Only for Use inside Japan and General Use outside Japan)
2.5
AC Cable Connection under a Free-Access Floor
(Only for Use inside Japan and General Use
outside Japan)
If AC cables are connected to the main unit, Extended I/O Cabinet, Extended Power
Cabinet, or Dual Power Feed Option under a free-access floor, it is recommended that
the underfloor height be 300 mm (11.8 in.) or more in consideration of the shape of
the AC cable connector, cable bending radius (see
However, if the underfloor height is less than 300 mm (11.8 in.), place outlets
sideways (see
The AC cables of the main unit, Extended Power Cabinet, and Extended I/O Cabinet
ACS each can be drawn about 2.5 m (9.8 in.) from the bottom of the unit. Prepare an
outlet near the unit by considering this pull-out length.
(1) When the underfloor height is 300 mm
Free-access
floor
Remark 1: In this figure, the main unit is shown as an example.
Remark 2: Values in ( ) are in inches.
U41631-J-Z816-5-76
Figure 2.31
(2)).
(11.8 in.) or more
Outlet
Figure 2.31 AC cable connection under a free-access floor

(only for use inside Japan and general use outside Japan)

Figure 2.31
(1)).
(2) When the underfloor height is less
than 300 mm (11.8 in.)
Free-access
floor
Outlet
Unit: mm (in.)
2-41