Fujitsu PRIMEQUEST 580A Installation Planning Manual page 59

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

Power supply
Input voltage tolerance and No. of phases
Frequency and tolerance
Maximum power
consumption/apparent power
Power factor
Inrush current [A] [Inrush duration] (*7)
Leakage current [mA] (*7)
CB/breaker capacity [A]
*1:
This value does not include any projection.
*2:
Value for the case the maximum allowable number of optional units is
mounted.
The weight of the unit based on the equipment configuration can be
calculated from the following formula:
*3:
There must be no condensation.
*4:
The temperature requirement depends on the installation altitude.
*5:
"Not operating" means the time when the equipment is stored.
*6:
The noise and sound power level vary on the ambient temperature.
*7:
These values are for each power cable.
*8:
If the intake air temperature is high (within the normal temperature) in
normal operation, the FAN rotate at high speed. [addition according to
the manual errata 2008/09/19]
U41631-J-Z816-5-76
Item
Unit weight = 264 + (42 x K)
K= Number of PCI_Boxes mounted:
- 5 to 35 °C (41 to 95.0 °F)
[if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)]
- 5 to 33 °C (41 to 91.4 °F)
[if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)]
- 5 to 32 °C (41 to 89.6 °F)
[if installed at an altitude of 2000 to 2500 m (6561.6 to 8202 ft)]
- 5 to 30 °C (41 to 86 °F)
[if installed at an altitude of 2500 to 3000 m (8202 to 9842.4 ft)]
Operating
Not operating
From a minimum of one to a
maximum of eight
1.3 Installation Specifications
Value
200 to 240 VAC ± 10 %
50/60 Hz +2/-4 Hz
5,890 W/6,000 VA
200 VA
0.9 or more
100 or less
4.4 or less
15
1-31

Advertisement