Fujitsu PRIMEQUEST 580A Installation Planning Manual page 49

Hide thumbs Also See for PRIMEQUEST 580A:
Table of Contents

Advertisement

*1:
This value does not include any projection.
*2:
Value for the case with the maximum number of optional units allowed
installed.
The weight of the unit based on the equipment configuration can be
calculated from the following formula:
When 32-GB memory is mounted, the formula is as follows:
*3:
When up to 2 TB-memory is mounted, the maximum heat dissipation is
24,200 KJ/h.
*4:
There must be no condensation.
*5:
The temperature requirement depends on the installation altitude.
*6:
"Not operating" means the time when the equipment is stored.
*7:
The noise and sound power level vary on the ambient temperature.
*8:
When up to 2 TB-memory is mounted, the maximum power consumption/
apparent power is 6,720 W/6,790 VA.
*9:
These values are for each power cable.
*10:
If the intake air temperature is high (within the normal temperature) in
normal operation, the FAN rotate at high speed. [addition according to
the manual errata 2008/09/19]
U41631-J-Z816-5-76
Unit weight = 464 + (12 x E) + (15 x F) + (1 x G) + (26 x H)
Unit weight = 464 + (13 x E) + (15 x F) + (1 x G) + (10 x H)
E = Number of SBs mounted:
F = Number of IOUs mounted:
G = Number of GSWBs or GTHBs mounted:
H = Number of Dual Power Feed Options mounted:
- 5 to 35 °C (41 to 95.0 °F)
[if installed at an altitude of 0 to 1500 m (0 to 4921.2 ft)]
- 5 to 33 °C (41 to 91.4 °F)
[if installed at an altitude of 1500 to 2000 m (4921.2 to 6561.6 ft)]
- 5 to 32 °C (41 to 89.6 °F)
[if installed at an altitude of 2000 to 2500 m (6561.6 to 8202 ft)]
- 5 to 30 °C (41 to 86 °F)
[if installed at an altitude of 2500 to 3000 m (8202 to 9842.4 ft)]
1.3 Installation Specifications
From a minimum of one to a
maximum of four
From a minimum of one to a
maximum of four
From a minimum of zero to a
maximum of two
From a minimum of zero to a
maximum of one
1-21