Power Supply Input Voltages
460W power supply module:
100 - 127 V at 50/60 Hz 5.8 A
200 - 240 V at 50/60 Hz 2.9 A
750W power supply module:
100 - 127 V at 50/60 Hz 8.2 A
200 - 240 V at 50/60 Hz 4.4 A
600W power supply module:
100 - 127 V at 50/60 Hz 5.8 A
200 - 240 V at 50/60 Hz 2.9 A
Power Supply Output Voltages
The following table lists the total wattage available from the power subsystem for each voltage. For
information about calculating the power usage for your configuration, please use the Power Budget
Tool.
System Environmental Specifications
The following table defines the system level operating and non-operating environmental limits.
Parameter
Temperature
Operating
Shipping
Altitude
Operating
Humidity
52
Table 5. Power Supply Output Capability
Voltage
Maximum Current
12V
12VSB
Table 6. System Environmental Limits Summary
ASHRAE Class A2 – Continuous Operation. 10ºC to 35ºC (50ºF to 95ºF) with the
maximum rate of change not to exceed 10°C per hour.
ASHRAE Class A3 – Includes operation up to 40ºC for up to 900 hrs per year.
ASHRAE Class A4 – Includes operation up to 45ºC for up to 90 hrs per year.
-40ºC to 70ºC (-40ºF to 158ºF)
Support operation up to 3050m with ASHRAE class deratings.
62.0A
2.1A
Limits
®
Intel