Co-Linear Venting - Valor Horizon 534ILN Installation And Operation Instructions Manual

Natural / propane gas direct vent gas fireplace heater
Table of Contents

Advertisement

Co-Linear Vent Installations
The chimney and fi replace opening sizes are shown in
Dimensions and Location sections of this manual.
Place the appliance (fi tted with the co-linear adapter)
near the fi replace opening but allow space for
manipulating the chimney liners on to the appliance.
Drop the 3-inch diameter fl exible liners into the
chimney from outside.
Fit the liners to the co-linear adapter paying attention to
inlet and exhaust and move the appliance to its proper
position. Be aware of the minimum liver bend radius
and maximum liner horizontal run shown on page 14 of
this manual.
Fit the termination kit and fl ashing to the exterior of the
chimney.
Secure the appliance to the fl oor or wall if necessary.
Rear or Top Outlet Conversion to Co-Linear Liners using Valor
556CLA Co-Linear Adapter.
(Generic co-axial to co-linear adapter boxes may also be used as an
alternate to the 556CLA).
Only for use when retrofi tting a solid-fuel burning fi replace and chimney.
The appliance must not be connected to a chimney fl ue serving a separate solid-
fuel burning appliance.
Requires 556CLA Co-Axial to Co-Linear Appliance Adapter (or, alternatively, a
generic adapter), two lengths of 3-inch diameter fl exible chimney liner, co-linear termination kit and fl ashing and either
high wind vertical vent terminal cap or a low profi le vertical termination. Zero Clearance stand-offs and shields supplied
with the heater are not required for this application.
556CLA Kit
10"
10"
7-5/8" dia.
collar
3" Inlet & Exhaust
Collars
559CLT Co-Linear Terminal
18
18

Co-Linear Venting

Co-Axial to Co-Linear Adapter
(alternate to 556CLA)
559FSK Flashing Kit
3" min.
2 x 3"
bend radius
liners
Co-linear
adapter
18" max.
horizontal run
Co-Linear installation into existing F/P
2 x 3" Liners
556CLA
14"
556CLA on
Rear Outlet
Alternate to 559CLT/559FSK Conversion
Terminal Cap
Approved co-linear
termination or approved
co-linear adapter
and approved
Flashing
co-axial
termination
Max.
40'
2 x 3"
534
liners
engine
Co-linear
adapter
556CLA
2 x 3" Liners
14"
556CLA on
Top Outlet
Co-Linear to Co-Axial
Adapter
Flashing