Dc Cable Connections; Figure 11, Dc Cable To Battery Terminals; Figure 12, Dc Cable To Inverter's Dc Terminals - Magnum Energy MMS1012 Owner's Manual

Mms series inverters/chargers
Hide thumbs Also See for MMS1012:
Table of Contents

Advertisement

DC Cable Connections

When connecting the DC cable to the battery or to the inverter's DC
terminals, the hardware should be installed in the correct order to
prevent high resistance connections from heating up and possibly
causing the connections to melt. Follow Figures 11 and 12 to stack
the hardware correctly. Tighten the terminal connections from 10 to
12 foot-pounds.
CAUTION: Don't put anything between the DC cable ring
lug and the battery terminal post or the inverter's DC
terminal. If antioxidant grease or spray is used, apply it
after all the connections have been made and are properly
tightened.
CAUTION: Overtightening or misthreading nuts on the DC
terminals will cause the bolts to strip and snap/break-off.
T em perature sensor
bolt
battery
post

Figure 11, DC Cable to Battery Terminals

CAUTION: The inverter is NOT reverse polarity protected
(negative and positive connected backwards). You must
verify the correct voltage polarity BEFORE connecting the
DC wires or damage may occur.
Crimped and sealed copper ring terminal lugs with a 5/16" hole should
be used to connect the DC wires to the inverter's DC terminals.
Inverter's
D C term inal

Figure 12, DC Cable to Inverter's DC Terminals

© 2010 Magnum Energy, Inc.
nut
lock w asher
B A T T ER Y
battery term inal
flat w asher
DC cable lugs are flush
with the battery terminals.
T orque the battery terminals
from 10 to 12 foot-pounds.
D C cable
w ith ring lug
" (Kep
5 /16
nut w ith star-w asher) or
F lange nut
2.0 Installation
D C cable
w ith ring lug
Verify that the
D C
term inal cover
(snaps on)
17

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mms1012-g

Table of Contents