Dc Ground Wire; Dc Negative Wire; Battery Temperature Sensor; Dc Positive Wire - Magnum Energy MMS1012 Owner's Manual

Mms series inverters/chargers
Hide thumbs Also See for MMS1012:
Table of Contents

Advertisement

CAUTION: The inverter is NOT reverse polarity pro-
tected. If this happens, the inverter will be damaged and
will not be covered under warranty.
the DC wires from the batteries to the inverter, verify
the correct battery voltage and polarity using a voltme-
ter. If the positive terminal of the battery is connected
to the negative terminal of the inverter and vice versa,
severe damage will result. If necessary, color code the
cables with colored tape or heat shrink tubing; RED for
positive (+), and BLACK for negative (-) to avoid polar-
ity confusion.
Info: The DC overcurrent device (i.e., fuse or circuit
breaker) must be placed in the positive (RED) DC cable
line between the inverter's positive DC terminal and
the battery's positive terminal (RED); as close to the
battery as possible.

DC Ground Wire

Route an appropriately sized DC grounding wire (GREEN or bare wire)
from the inverter's DC Ground Terminal (see Figure 3, Item 11) to a
dedicated system ground. Recommended tightening torque is 45 in.
lbs.

DC Negative Wire

Route an appropriately sized DC negative wire (BLACK) from the
negative terminal of the fi rst battery string to the inverter's negative
terminal (see Figure 21 for reference).

Battery Temperature Sensor

Connect the RJ11 connector end of the BTS to the ACCESSORY PORT
(see Figure 4, Item 15) on the inverter. Connect the other end of the
BTS to the negative terminal of the fi rst battery string (in same place as
the negative DC wire above); refer to Figure 11 for the correct hardware
placement.

DC Positive Wire

Mount the DC fuse block and disconnect (or circuit breaker assembly)
as near as practical to the batteries, and then open the disconnect
(or circuit breaker).
WARNING: DO NOT close the DC fuse/DC disconnect (or
close the DC circuit breaker) to enable battery power to
the inverter at this time. This will occur in the Functional
Test after the installation is complete.
Route and connect an appropriately sized DC positive wire (RED) from
the DC fuse block (or circuit breaker assembly) to the inverter's posi-
tive DC terminal.
© 2010 Magnum Energy, Inc.
2.0 Installation
Before connecting
19