2.0 Installation

DC Cable Connections

When connecting the DC cable to the battery or inverter DC terminals,
the hardware should be installed in the correct order to prevent high
resistance connections which will heat up and could cause the connec-
tions to melt. Follow Figures 9 and 10 to stack the hardware correctly.
Tighten the terminal connections from 10 to 12 foot-pounds.
CAUTION: Do not put anything between the DC cable ring
lug and the battery terminal post or inverter's DC terminal.
If antioxidant grease or spray is used, apply it after all the
connections have been made and are properly tightened.
CAUTION: Overtightening or misthreading nuts on the DC
terminals will cause the bolts to strip and snap/break-off.
battery
post

Figure 9, DC Cable to Battery Terminals

CAUTION: The inverter is NOT reverse polarity protected
(negative and positive connected backwards). You must
verify the correct voltage polarity BEFORE connecting the
DC wires or damage may occur.
Crimped and sealed copper ring terminal lugs with a 5/16" hole should
be used to connect the DC wires to the inverter's DC terminals.

Figure 10, DC Cable to Inverter's DC Terminals

14
Temperature sensor
(for charger models)
nut
lock washer
battery terminal
flat washer
bolt
Inverter's
DC terminal
(nut with star-washer)
DC cable
with ring lug
BATTERY
Verify that the
DC cable lugs are flush
with the battery terminals.
Torque the battery terminals
from 10 to 12 foot-pounds.
DC cable
with ring lug
DC
terminal cover
(snaps on)
½" Kep nut
© 2010 Magnum Energy, Inc.