2.0 Installation

DC Cable Connections

When connecting the DC cable to the battery or to the inverter's DC
terminals, the hardware should be installed in the correct order to
prevent high resistance connections from heating up and possibly
causing the connections to melt. Follow Figures 9 and 10 to stack
the hardware correctly. Tighten the terminal connections from 10 to
12 foot-pounds.
CAUTION: Do not put anything between the DC cable ring
lug and the battery terminal post or inverter's DC terminal.
If antioxidant grease or spray is used, apply it after all the
connections have been made and are properly tightened.
CAUTION: Overtightening or misthreading nuts on the DC
terminals will cause the bolts to strip and snap/break-off.
T em perature sensor
bolt
battery
post

Figure 9, DC Cable to Battery Terminals

CAUTION: The inverter is NOT reverse polarity protected
(negative and positive connected backwards). You must
verify the correct voltage polarity BEFORE connecting the
DC wires or damage may occur.
Crimped and sealed copper ring terminal lugs with a 5/16" hole should
be used to connect the DC wires to the inverter's DC terminals.
Inverter's
D C term inal

Figure 10, DC Cable to Inverter's DC Terminals

14
nut
lock w asher
B A T T ER Y
battery term inal
flat w asher
DC cable lugs are flush
with the battery terminals.
T orque the battery terminals
from 10 to 12 foot-pounds.
D C cable
w ith ring lug
" (Kep
5 /16
nut w ith star-w asher) or
F lange nut