Ac Input Wiring; Table 4, Minimum Wire Size To Circuit-Breaker Size - Magnum Energy MM AE Series Owner's Manual

Table of Contents

Advertisement

Overcurrent protection must be provided by fuses or circuit-breakers,
and must
be properly sized and rated for the wire they are protecting
and the appliances being powered.
An external disconnect device is required for both the AC input and
AC output wiring. Most inverter's that are "hardwired" use a service/
distribution panel wired to the inverter's input (main panel), and a
dedicated panel between the inverter's output wiring and the AC loads
(sub-panel). These systems use the circuit breakers provided in the
panels as the overcurrent protection and the AC disconnect. If fuses
are used, then separate AC disconnect switches will be needed.
Based on information from the NEC, Table 4 provides the minimum
AC wire size and the suggested breaker size based on the inverter
model.
However, larger wire size may be required because of volt-
age drop. The
AC wire sizes provided in this table assume using only
copper wire and a temperature rating of 75° C or higher. A minimum
of #14 AWG is required for all AC wiring.

Table 4, Minimum Wire Size to Circuit-breaker Size

Inverter
Input
Model
Breaker
MM612AE
7 amps
MM1512AE 20 amps #12 AWG
MM1524AE 20 amps #12 AWG

AC Input Wiring

Your inverter has an AC transfer feature that passes the AC input
power to the inverter's output. Connection to the AC input is made
by hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from the
AC distribution panel) through a strain relief on the AC IN opening.
Refer to Table 4 for minimum wire size and overcurrent protection
required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC
cable, and then separate the three wires and strip about 3/4" of
insulation from each wire.
3. Using approved AC wire connectors, connect the incoming Hot
In, Neutral In, and Ground wires to the MM-AE Series' AC wires
colored black (HOT IN), white (NEU IN), and green (AC GROUND)
respectively.
4. After making the AC input connections, secure the AC input cable
by tightening the strain relief.
The AC input wiring in the inverter is complete. Review all AC wiring
to ensure all connections are correct and secure.
© 2010 Magnum Energy, Inc.
AC Input
Suggested
Minimum
Breaker
Wire Size
Size
#14 AWG
10 amps
20 amps
20 amps
2.0 Installation
AC Output
Suggested
Output
Minimum
Breaker
Breaker
Wire Size
8 amps
#14 AWG
10 amps
12 amps #14 AWG
15 amps
12 amps #14 AWG
15 amps
Size
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

Mm1512aeMm1524aeMm 612ae

Table of Contents