AC Input Wiring

Your inverter has an AC transfer feature that passes the AC input
power to the inverter's output. Connection to the AC input is made by
hardwiring from a distribution panel as described below:
1. Run an appropriately sized 2-conductor plus ground cable (from
the AC distribution panel) through a strain relief on the AC IN open-
ing. Refer to Table 4 for minimum wire size and overcurrent protection
required for the AC input wiring.
2. Remove about two inches of the insulating jacket from the AC cable,
and then separate the three wires and strip about 3/4" of insulation
from each wire.
3. Using approved AC wire connectors, connect the incoming Hot In,
Neutral In, and Ground wires to the MM Series' AC wires colored black
(HOT IN), white (NEU IN), and green (AC GROUND) respectively.
4. After making the AC input connections, secure the AC input cable
by tightening the strain relief.
The AC input wiring in the inverter is complete. Review all AC wiring to
ensure all connections are correct and secure.
Neutral
In
(white)
Hot
In
(black)
© 2010 Magnum Energy, Inc.
AC
Ground
In/Out
(green)
Strain
reliefs
AC IN

Figure 11, AC Wiring Connections

2.0 Installation
Neutral Out
(white w/black
stripe)
Hot
Out
(red)
AC OUT
19