Test Of Ignition Safety System; Perform Test Of Low Water Cut O; Perform Test Of Limit Controls - FULTON Caliber Installation And Operation Manual

High efficiency hydronic boilers 300,000 - 850,000 btu/hr
Table of Contents

Advertisement

SECTION 3
CAL-IOM-2012-1220
3. Review the unit-speci c control schematics, and follow appropriate
instructions.

Test of Ignition Safety System

Test the ignition system safety shuto as follows:
1. Remove the black plug/connector from the main gas valve (it is held on
with a central screw).
2. With the main gas cock (inlet manual gas valve) open, the burner should
be cycled on. After all the safety limits such as gas pressure, water ow and
temperature are satis ed, the blower will run and pre-purge the boiler.
3. Once the purge is complete (15-30 seconds), the ignition transformer will
be energized. There will be a 4 second trial for ignition period.
4. The main gas valve will not open because there is no power to the valve
due to the disconnected wires. Hence, no ame will be established and the
ame safeguard will not receive a ame signal from the UV scanner.
5. After 4 seconds, the ame safeguard programmer will assume a "Flame
Failure" condition and go to a "lockout" mode. Lockout will require manual
reset of the ame safeguard. The control will allow one retry before locking
out.
6. After completing this test, turn o the boiler and reconnect the wires to
the main gas valve.
Perform Test of Low Water Cut Off
This boiler is equipped with a ow switch type low water cut-o in the outlet
nozzle. Once the boiler is full of water the following test can be accomplished:
1. Turn the boiler o .
2. Turn system pump o .
3. Turn the boiler back on. Boiler will begin to pruge, at which point it will
lock out, annunciating "ilk o : ow switch". Reset lockout, and turn pump
back on.
4. Perform appropriate test for any external or factory-installed probe-type
low water cut-o .

Perform Test of Limit Controls

Fire the boiler and test the high limit control as follows:
1. Access the High Limit screen of the SOLA control.
2. Alter high temperature limit to a value lower than the anticipated loop
temperature. Turn the boiler on. Water temperature will rise until the
boiler locks out. This condition has to be manually reset. Alter the high
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
OPERATION
!
WARNING
Do not attempt to start the boiler for
any testing before lling and purging
the boiler. A dry re will seriously
damage the boiler and may result in
property damage or personnel injury
and is not covered by warranty.
Before commissioning the boiler,
verify with authorized personnel that
the gas lines have been purged.
Never attempt to operate a boiler
that has failed to pass all the safety
checks.
Never leave an opened manual air
vent unattended. In the event an
opened vent is left unattended, water
damage could occur.
Check daily that the equipment area
is free and clear of any combustible
materials, including ammable
vapors and liquids.
4
CAUTION
Do not use this equipment if any part
has been under water (or subjected to
heavy rains/water if the equipment
does not have NEMA 4 wiring, controls
and instrumentation). Immediately
call a quali ed service technician to
inspect the equipment and to replace
any part of the control system and/or
gas control(s) which have been under
water.
Commissioning/Start up by a non-
Fulton authorized person will void the
product warranty.
Please read these instructions and
post in an appropriate place near the
equipment. Maintain in good legible
condition.
3-3