Setting Combustion - FULTON Caliber Installation And Operation Manual

High efficiency hydronic boilers 300,000 - 850,000 btu/hr
Table of Contents

Advertisement

OPERATION
!
WARNING
Non-Fulton product information is for
reference purposes only. No Fulton
document should substitute for full
review of documentation available
from the component manufacturer.
This boiler is equipped with an
ignition device which automatically
lights the burner. Do not try to light
burner by hand.
3-6

SETTING COMBUSTION

To Set Combustion, perform the following:
1. Obtain the following tools: Calibrated combustion analyzer, manometer to
measure inlet gas pressure.
2. From home screen tap "Operation. "
3. Tap the yellow background "rpm" box next to ring rate.
4. Under "Firing Rate Control" tap "Manual in Run. " Refer to Figure 12.
FIGURE 12 SETTING COMBUSTION ON SOLA CONTROL
5. Using test re sheet enter the light o rpm's in the "Manual Firing Rate" box.
6. Once the rpm's are entered tap "OK", then return to the home screen.
7. Turn the local/o /remote switch to the local position.
8. Once burner has started and you have veri ed ame signal return to the
"Manual Firing Rate" box.
9. Increase the ring rate in 500 rpm increments until you reach the high re
rpm's from the factory test re sheet.
10. At each point check combustion. CO2/CO should remain constant
throughout ring range.
11. Monitor inlet gas pressure during combustion.
12. Once the high re rpm setting is reached make ne tuning adjustments on
the gas ratio valve " ow rate" to match factory test re settings. The " ow
rate" adjustment requires a 3mm hex wrench.
NOTE: Turning the screw counterclockwise increases gas ow, clockwise
decreases gas ow.
SECTION 3
CAL-IOM-2012-1220
© The Fulton Companies 2012