Appendix C - Preventive Maintenance

Recommended Inverter and Battery Care

The MM Series inverter is designed to provide you with years of
trouble-free service. Even though there are no user-serviceable parts,
it is recommended that every 6 months you perform the following
maintenance steps to ensure optimum performance and extend the
life of your batteries.
WARNING: Prior to performing these checks, switch both
the AC and DC circuits OFF.
Visually inspect batteries for cracks, leaks, or swelling – replace if
necessary.
Use baking soda to clean and remove any electrolyte spills or
buildups.
Check and tighten all battery hold down clamps.
Clean and tighten (10 to 12 foot-pounds) all DC terminals (battery
and inverter) and connecting cables.
Check and fi ll battery water levels (Liquid Lead Acid batteries
only).
Check individual battery voltages (replace those that vary more
than 0.3 VDC of each other).
Check all cable runs for signs of chafi ng – replace if necessary.
Check the inverter's cooling vents – clean as necessary.

RV/Marine Off-Season Storage

When placing your coach or boat into seasonal storage, it is recom-
mended that you perform the following to ensure the system is prop-
erly shut down (or properly confi gured for seasonal storage). This is
especially important for maintaining the batteries.
Perform the recommended maintenance steps noted above.
Fully charge the batteries.
Connect shore power (if available) and verify that the breaker to
the battery charger is switched ON.
Verify the inverter is switched OFF.
Switch OFF all unnecessary AC and DC loads.
© 2010 Magnum Energy, Inc.
Appendix C - Preventive Maintenance
35