3 Description
3.1 General
Gas 100 Eco 115 / 65 boilers are floor standing gas-fired condensing
boilers fitted with an "Open Therm" control interface which enable
direct weather compensation using Remeha single and multi boilers
controls or the customer can choose to use external control options
supplied by others without affecting boiler performance.
They are designed for closed circuit hot water boiler rooms with a
maximum operating temperature of 90°C. However, open vented
systems can be accommodated.
3.2 Homologations
3.2.1
General instructions
Flue gas discharge
3.2.2
Gas categories
Gas 110 Eco 65
Gas 110 Eco 115
Gas 110 Eco 65
Gas 110 Eco 115
6
Boiler
No. CE
Type
Ignition
Gas
Category
II
Category
II
See chapter 5.2 "Important comments on the treatment of the
heating circuit".
Installation is recommended on low temperature heating installations
(Underfloor heating, radiators, ...).
B
23
Type of gas used
Natural gas
2H3P
Propane
Type of gas used
Natural gas
2H3P
Propane
Gas 110 Eco 115 / 65
Gas 110 Eco 65 / Gas 110 Eco 115
CE-0063BS3826
- C
- C
- C
- C
- C
- C
13
33
43
53
63
Chimney / Flue gas outlet
Automatic
Natural gas / Propane
Supply pressure (Gas pressure when the boiler
is not operating)
Maximum allowed on the gas valve
40 mbar
60 mbar
Working pressure
Minimum
17 mbar
25 mbar
- C
83
93
Maximum
25 mbar
57.5 mbar
25/01/2011 - 300014883-001-K