4.6.14 Maximum delay time ( )

Adjustable from
to
minutes.
This value sets the maximum off time following a control stop. The
minimum off time is preset to a fixed value (150 seconds).
A combination of both values is used to prevent hunting taking place.

4.6.15 Start and end point analog signal (

and
)
Start point (0 V): adjustable between
(-50) °C and +
°C.
This value sets the required flow temp at 0 V signal input (restricted
by the minimum flow set point).
End point (10 V): adjustable between +
°C and
(+299)
°C.
This value sets the required flow temp at 10 V signal input (restricted
by the maximum flow set point).
NOTE: These settings are only applicable when boiler control
operation parameter (
) has the
value set to
.
24
Gas 110 Eco 115 / 65
25/01/2011 - 300014883-001-K