3.7 Hydraulic specifications
Depending on the flow, the following diagrams represent:
- the manometric heights of the heating
- loss of load in the boiler.
For a fixed flow, the manometric height available at the boiler outlet
is obtained by taking the difference between the manometric height
of the circulator pump and the loss of load in the boiler.
Optional 3-speed circulator pump for Gas 110 Eco 65 - UPS 25-70 130
A. Rated net head (mWG)
3
B. Flow rate (m
/h)
Optional 3-speed circulator pump for Gas 110 Eco 115 - UPS 25-80 130
A. Rated net head (mWG)
3
B. Flow rate (m
/h)
C. Loss of load Gas 110 Eco 115
25/01/2011 - 300014883-001-K
For example: Gas 110 Eco 65 with UPS 25-70 130 pump:
manometric height available at 2.61 m
mWG (i.e. 3 mbar)
3
2.61 m
/h corresponds to a load of 61 kW and a
C. Loss of load Gas 110 Eco 65
Gas 110 Eco 115 / 65
3
/h = 4.6 mWG - 1.6 mWG = 3
∆
t of 20 K
13