Programming Boiler Control; Instruct The User Of The Boiler; Shut-Down - REMEHA Gas 110 Eco 115 Installation, User And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for Gas 110 Eco 115:
Table of Contents

Advertisement

When the setting is correct:
Press the [+] and [-]-keys simultaneously to return in operating
mode.
Remove the measuring equipment.
Replace the plastic cap onto the measuring tube.
Only make small adjustments 1/8 turns when adjusting
minimum outputs (4).
If the values exceed the tolerances:
Check the gas input pressure.
Check that the restrictor fitted is suitable for the gas being
used (G20 = Diameter 8.6, Propane = 6.7).

7.4 Programming boiler control

Set the integrated control in compliance with the corresponding
operating instructions.

7.5 Instruct the user of the boiler

7.6 Shut-down

Temporary shut-down with frost protection
- Do not isolate the electric power supply.
- Do not close the gas cock.
- Use the switch function - sets controls to off: use
-symbol.
See chapter 4.1.3
Permanent shut-down without frost protection
- Set system controls to off.
- Isolate the electric power supply.
- Close the gas cock.
- Drain the system.
42
-key and
Gas 110 Eco 115 / 65
25/01/2011 - 300014883-001-K