Gas Type - REMEHA Gas 110 Eco 115 Installation, User And Service Manual

Gas fired condensing boiler
Hide thumbs Also See for Gas 110 Eco 115:
Table of Contents

Advertisement

Gas 110 Eco 115
Changing from Natural Gas to Propane requires:
- Installing the conversion kit (fitting instructions in kit),
- the setting of the burner,
- the setting of the maximum fan speed.
Isolate main power supply.
Put the gas block and restrictor in place
See Assembly instructions, Propane conversion kit.
Re-establish power supply to burner and controls.
Set the maximum fan speed to a value of:
- 6700 rpm: Gas 110 Eco 115
See chapter 4.6.3 and § 4.6.4 for speed at full load HTG
and DHW
Take the boiler up to maximum power.
- Press key
and [+] simultaneously for 2 seconds.
" "
: Maximum power of the burner
Remove the plastic cap from the measurement tube.
Measure the CO
or O
2
2
See table on page 40
Check the flame via the flame inspection window. It must not go
out. The flame must be stable and blue in colour with orange
particles around the edge of the burner.
Press
and [-]-keys simultaneously.
" "
: Minimum output.
Measure the CO
or O
2
2
Modify the "min output" setting with the setting screw
See table on page 40

9.2 Gas type

Affix the adjusted for sticker which can be found in the LPG
conversion pack and indicate for which type of gas the boiler is fitted
and set to.
25/01/2011 - 300014883-001-K
level in the flue gases.
level in the flue gases.
Check the output delivered again.
Adjust if necessary.
When the setting is correct:
Press the [+] and [-]-keys simultaneously to return in operating
.
mode.
Remove the measuring equipment.
Replace the plastic cap onto the measuring tube.
Gas 110 Eco 115 / 65
47