Powerware 9330 Installation & Operation Manual page 215

10–20 kva/25–40 kva
Table of Contents

Advertisement

I/O
CABINET
P/O TB1
A
B
C
MAINS IN
480V
(208V, 600V
OPTIONAL)
GND
P/O
4- -POLE
GND BLK
P/O TB1
A
B
C
N
BYPASS IN
480V
(208V, 600V
OPTIONAL)
OPTIONAL
42 CIRCUIT
GND
DISTRIBUTION
L1
L2
L3
P/O TB1
A
B
C
AC LOAD OUT
208/120V
N
P/O TB1
NEUTRAL TO
GND
GND BOND
P/O
4- -POLE
GND BLK
P/O = PART OF
CONFIGURATION
DUAL FEED; DUAL INPUT TRANSFORMERS;
BYPASS SWITCH; WITH DISTRIBUTION
CONFIGURATION
SINGLE FEED; INPUT TRANSFORMER;
BYPASS SWITCH; WITH DISTRIBUTION
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 Rev. N 013004
X2
H2
H21
H22
H23
X1
H1
H11
H12
H13
MAIN ISO
XFMR
X2
H2
H21
H22
H23
X1
H1
H11
H12
H13
BYPASS
ISO XFMR
N
CB2
OUTPUT
BREAKER
2
1
4
3
6
5
150A
UPS SYSTEM OPTIONS CABINET CONFIGURATIONS
POWERWARE 9330 (25 kVA---40 kVA)
WITH ISOLATION TRANSFORMERS
CONFIGURATION
DUAL FEED; DUAL INPUT TRANSFORMERS;
BYPASS SWITCH; WITHOUT DISTRIBUTION
CONFIGURATION
SINGLE FEED; INPUT TRANSFORMER;
BYPASS SWITCH; WITHOUT DISTRIBUTION
OPTIONAL
BREAKER
1
H33
3
H32
H31
H3
5
X3
X0
H33
H32
H31
H3
X3
X0
3
4
1
7
8
5
11
12
9
SW1
EXT. WRAP
BYPASS
DESCRIPTION:
OPTIONS CABINET SCHEMATICS
DRAWING NO:
164201300---7
REVISION:
N
INTER- -
CABINET
WIRING
CB1
INPUT
2
4
6
150A
GND
CB3
BYPASS
BREAKER
150A
1
2
3
4
5
6
SHEET:
10 of 18
DATE:
013004
UPS
CABINET
MAINS
IN
A
E1
B
E2
C
E3
GND
A
E6
B
E7
C
E8
N
E12
BYPASS
IN
A
E9
B
E10
C
E11
N
E12
AC LOADS
OUT
A ---41