Powerware 9330 Installation & Operation Manual page 179

10–20 kva/25–40 kva
Table of Contents

Advertisement

Basic unit ratings at
0.7 lagging PF load
AC Output from
AC Output from
AC
Output Transformer
OUTPUT
OUTPUT
to Critical Load
to Critical Load
(0.95min.PF)
(0.95min.PF)
3 , 1 Neutral, 1 gnd
Basic unit ratings at
0.7 lagging PF load
AC Output from Output
AC
AC
to Critical Load
OUTPUT
(0 95min PF)
(0.95min.PF)
3 , 1 Neutral, 1 gnd
NOTE:
Callout letter
map to drawing #164201300---6
Powerware 9330 (10 kVA- -40 kVA) Installation and Operation
164201300 Rev. N 013004
Table E. Ratings & External Wiring Requirements for
Powerware 9330 (10 kVA---20 kVA)
Options Cabinet OUTPUT Transformer
g
Series/
Model
20/10
20/10
20/15
20/15
g
20/20
D
20/20
Table F. Ratings & External Wiring Requirements for
Powerware 9330 (10 kVA---20 kVA)
Options Cabinet OUTPUT Without Output Transformer
g
Series/
Model
p
p
20/10
20/15
D
20/20
and
,
,
,
Ratings 50/60 Hz
Voltage
Input
Output
kVA/KW
9.5/6.65
208/220
9.5/6.65
208/220
14.25/10
208/220
14.25/10
208/220
19/13.3
208/220
19/13.3
208/220
Ratings 50/60 Hz
Voltage
Input
Output
kVA/KW
10/7
208/220
208/220
15/10.5
208/220
208/220
20/14
208/220
208/220
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION:
L
Conductor
Output
Output
Minimum
Current
Size
(Amps)
208
26.4
10
480
11.4
14
208
39.6
8
480
17
12
208
52.7
6
480
22.8
10
Conductor
Output
Output
Minimum
Current
Size
(Amps)
27.8
8
41.6
6
55.5
4
SHEET:
DATE:
041503
4 of 17
A ---5

Advertisement

Table of Contents
loading

Table of Contents