9.
Terminals are UL and CSA rated at 90˚C. Refer to Tables N through Q for power cable
terminations, and Tables R through U for conduit requirements. Drawings 164201300---8
through 164201300---12 show the location of the power cable terminals inside the UPS,
Options, and Battery Cabinets.
Table N. UPS Cabinet Power Cable Terminations Powerware 9330 (10 kVA---20 kVA)
Terminal Function
AC Input to UPS
p
Rectifier and Bypass
(Single Input)
(Single Input)
AC Input to UPS
p
Rectifier (CB1)
(Dual Input)
(Dual Input)
AC Input To Bypass
p
(Dual Input)
Single Feed Jumper
g
on Bypass Input
Terminal Block
Terminal Block
AC Output to Critical
p
Load
DC Input from
Battery to UPS
y
External Battery
Input to UPS
Customer Ground
NOTE: Customer ground, size 1/0, can
be run in any conduit listed in
Tables R and S.
A ---10
Terminal
Function
E6
Phase A
E7
Phase B
E8
Phase C
E12
E1
Phase A
C
E2
Phase B
E3
Phase C
yp
E6
Phase A
E7
Phase B
E8
Phase C
E12
p
Phase A
Phase B
Phase C
E9
Phase A
E10
Phase B
E11
Phase C
E12
N/A
N/A
y
E4
Positive
S
E5
Negative
Ground
Ground
Size of Pressure
Termination
1 --- #14---2/0
1 --- #14---2/0
1 --- #14---2/0
Neutral
1 --- #8---2/0
1 --- #14---#3
1 --- #14---#3
1 --- #14---#3
1 --- #14---2/0
1 --- #14---2/0
1 --- #14---2/0
Neutral
1 --- #8---2/0
N/A
N/A
N/A
1 --- #8---2/0
1 --- #8---2/0
1 --- #8---2/0
Neutral
1 --- #8---2/0
Battery
Red Battery
(+)
Connector
Battery
Black Battery
(---)
Connector
1 --- #8---2/0
1 --- #8---2/0
2 --- #14---1/0
DESCRIPTION:
POWER WIRING INSTALLATION NOTES
DRAWING NO:
164201300---1
REVISION: N
Tightening Torque
N-M (lb-in.)
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
2.5 (22)
2.5 (22)
2.5 (22)
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
13.5 (120)
3/16 in. Hex
6 (50)
1/4–20 Stud
6 (50)
1/4–20 Stud
6 (50)
1/4–20 Stud
13 (110)
3/16 in. Hex
13 (110)
3/16 in. Hex
13 (110)
3/16 in. Hex
13 (110)
3/16 in. Hex
N/A
N/A
13 (110)
3/16 in. Hex
13 (110)
3/16 in. Hex
5.6 (50)