How To Check - Toshiba Super MMU-AP0092H Service Manual

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

9-2. How to check

On the remote controller (Remote controller, Central control remote controller) and on the interface P.C. board of the outdoor unit, LCD display part (Remote controller) or 7-segment
display part (on outdoor interface P.C. board) is provided in order to display the operation status.
When a trouble occurred, the method to judge the trouble or defective position of the air conditioner by this self-diagnosis function is shown below.
The following table shows the list of each check code that each device detects. Check the check contents in the following table according to position to be checked.
• Check from the indoor remote controller or TCC-LINK central controller: Refer to "Display on remote controller & TCC-LINK central controller" in the following table.
• Check from outdoor unit: Refer to "Display of outdoor segment" in the following table.
• Check from indoor unit of wireless remote controller: Refer to Sensor lamp display" in the following table.
Check code display list (Indoor unit)
[Indoor unit detects error.]
Check code display
TCC-LINK central
AI-NET central
& remote controller
(Network adapter use)
E03
97
E04
04
E08
96
E08 Duplicated indoor unit No.
E10
CF
E18
97, 99
F01
OF
F02
Od
F03
93
F10
OC
F29
12
L03
96
L07
99
L08
99
L08
L09
46
L20
98
L30
b6
L30 Detected indoor unit No.
P01
11
P10
Ob
P10 Detected indoor unit No.
P12
11
P31
47
Note) The check code display may be different according to the detected device even same error contents such as communication error.
Sensor lamp display
Outdoor 7-segment
Block display (∗)
Auxiliary code
Operation Timer Ready Flash
l
l
¥
l
l
¥
l
l
¥
l
l
¥
l
l
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
¥
¡
¥
¥
¡
¥
l
¥
¥
l
¥
¥
l
¥
¥
l
¥
¥
(∗) ¡: Goes on, ¥: Flashes, l: Goes off
A (Alternate)
S (Simultaneously) : Two LED flash simultaneously when there are two flashing LED.
Main defective position
Regular communication error between indoor
and remote controller
Regular communication error between indoor
and outdoor
Duplicated indoor address
Communication error between indoor MCU
Regular communication error between header
and follower in indoor unit
A
Indoor heat exchanger temp. sensor (TCJ) error
A
Indoor heat exchanger temp. sensor (TC2) error
A
Indoor heat exchanger temp. sensor (TC1) error
A
Room tem. Sensor (TA) error
S
Indoor or other P .C. board error
S
Duplicated setting of header in indoor group
S
There is group cable in individual indoor unit.
S
Indoor group address is unset.
S
Indoor capacity is unset.
S
Duplicated central control system address
S
External error was input in indoor (Interlock).
A
Indoor AC fan error
A
Indoor overflow was detected.
A
Indoor DC fan error
A
Other indoor unit error
: Flashing condition is alternate when there are two flashing LED.
Description
No communication from remote controller and network adapter
(No central control system communication also)
No communication from outdoor unit
An address same to self address was detected.
Communication error between MCU of main motor microprocessors
Regular communication between header and follower units in indoor unit
was impossible.
Open/short of heat exchanger temp. sensor (TCJ) was detected.
Open/short of heat exchanger temp. sensor (TC2) was detected.
Open/short of heat exchanger temp. sensor (TC1) was detected.
Open/short of room temp. sensor (TA) was detected.
Indoor EEPROM error (Other error may be detected.)
There were multiple header units in a group.
There is even an indoor unit connected to group in individual indoor unit.
Indoor group address is unset. (Detected also at outdoor unit side)
Capacity of indoor unit is unset.
Setting of central control system address is duplicated.
System abnormally stopped by input of external error (CN80).
Error of indoor AC can was detected. (Fan motor thermal relay operation)
Float switch operated.
Error (Over-current, lock, etc.) of indoor DC fan was detected.
Group follower unit cannot be operated by [E03/L03/L07/L08] alarm of
header unit.