Toshiba Super MMU-AP0092H Service Manual page 122

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

<Make a note of the setup contents. (Item code list (Example))>
DN
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
Existence of automatic
0d
COOL/HEAT mode
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
Louver type
19
(wind direction adjustment)
Temperature range of cooling/heating
1E
automatic SW control point
28
Power failure automatic recovery
2A
Option/Abnormal input (CN70) SW
31
Ventilation fan (standalone)
Sensor SW
32
(Selection of static pressure)
5d
High ceiling SW
Timer setting
60
(wired remote controller)
F0
Swing mode
F1
Louver fixing position (Flap No. 1)
F2
Louver fixing position (Flap No. 2)
F3
Louver fixing position (Flap No. 3)
F4
Louver fixing position (Flap No. 4)
Type
Item code [10]
Setup
data
0000
1-way Air Discharge Cassette
0001
4-way Air Discharge Cassette
∗1, ∗2
0002
2-way Air Discharge Cassette
1-way Air Discharge Cassette
0003
(Compact type)
0004
Concealed Duct Standard
0005
Slim Duct
0006
Concealed Duct High Static Pressure
0007
Under Ceiling
0008
High Wall
0009
0010
Floor Standing Cabinet
0011
Floor Standing Concealed
0012
0013
Floor Standing (Below 6HP)
0014
Compact 4-way Air Discharge Cassette
∗1 The initial setup value of EEPROM installed on the service P .C. board
∗2 <Model Name: MMU-AP
For the above models, set CODE No. to
Item
Type
MMU-AP
MMU-AP
MMU-AP
MMU-AP
MMD-AP
MMD-AP
MMD-AP
MMD-AP
MMC-AP
MMK-AP
MML-AP
MML-AP
MMF-AP
MMU-AP
2H>
+-
"
"
and the setting data 0000 (initial) to "0001".
Setting data
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0001: No auto mode
cooling/heating
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
0003: 3 deg (Ts ± 1.5)
0000: None
0002: Humidifier
0000: Not available
0000: Body sensor
0000: Standard
0000: Available
0001: Standard
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: Not fixed
Indoor unit capacity
Item code [11]
Model
Setup
abb. name
data
SH
0000*
0001
2H
0002
WH
0003
0004
YH
0005
BH
0006
SPH
0007
SH
0008
H
0009
H
0010
H
0011
0012
H
0013
BH
0014
0015
H
MH
122
Factory-set value
∗ Automatically selection by
connected outdoor unit
Setup
Model
data
Invalid
0016
007 type
0017
048 type
0018
056 type
009 type
0019
0020
012 type
0021
072 type
0022
015 type
0023
096 type
0024
018 type
0025
0026
024 type
0027
027 type
0028
~
030 type
0034
036 type
Model

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents