Toshiba Super MMU-AP0092H Service Manual page 97

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
Check code
Auxiliary code
controller
E31
E31
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 errors
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error or communication error
between IPDU and I/F P .C. board or
outdoor I/F P .C. board error
F01
F02
F03
F04
F04
F05
F05
F06
F06
F07
F07
F08
F08
F10
F12
F12
F13
F13
01: Compressor 1 side
02: Compressor 2 side
Detected
Check code name
Status
position
I/F
IPDU communication error
All stop
Indoor unit
Indoor TCJ sensor error
Corresponding
unit only stops.
Indoor unit
Indoor TC2 sensor error
Corresponding
unit only stops.
Indoor unit
Indoor TC1 sensor error
Corresponding
unit only stops.
I/F
TD1 sensor error
All stop
I/F
TD2 sensor error
All stop
All stop
I/F
TE1 sensor error
I/F
TL sensor error
All stop
I/F
TO sensor error
All stop
Indoor
Indoor TA sensor error
Corresponding
unit only stops.
I/F
TS1 sensor error
All stop
All stop
IPDU
TH sensor error
Error detection condition
Communication of each IPDU
• Check connection of communication connector and
(P .C. board) in inverter box interrupted.
disconnection between IPDU and I/F P .C. board.
• Check outdoor P .C. board (I/F, IPDU, Fan IPDU) error.
• Check external noise.
• Resistance value of sensor is infinite
• Check connection/cabling of TCJ sensor connector.
or zero. (Open/Short)
• Check characteristics of TCJ sensor resistance value.
• Check indoor P .C. board error.
• Resistance value of sensor is infinite
• Check connection/cabling of TC2 sensor connector.
or zero (Open/Short).
• Check characteristics of TC2 sensor resistance value.
• Check indoor P .C. board error.
• Resistance value of sensor is infinite
• Check connection/cabling of TC1 sensor connector.
or zero (Open/Short).
• Check characteristics of TC1 sensor resistance value.
• Check indoor P .C. board error.
• Resistance value of sensor is infinite
• Check connection of TD1 sensor connector.
or zero (Open/Short)
• Check characteristics of TD1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Resistance value of sensor is infinite
• Check connection of TD2 sensor connector.
or zero (Open/Short)
• Check characteristics of TD2 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Resistance value of sensor is infinite
• Check connection of TE1 sensor connector.
or zero (Open/Short).
• Check characteristics of TE1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Resistance value of sensor is infinite
• Check connection of TL sensor connector.
or zero (Open/Short).
• Check characteristics of TL sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Resistance value of sensor is infinite
• Check connection of TO sensor connector.
or zero (Open/Short).
• Check characteristics of TO sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Resistance value of sensor is infinite
• Check connection/cabling of TA sensor connector.
or zero (Open/Short).
• Check characteristics of TA sensor resistance value.
• Check indoor P .C. board error.
• Resistance value of sensor is infinite
• Check connection of TS1 sensor connector.
or zero (Open/Short).
• Check characteristics of TS1 sensor resistance value.
• Check outdoor P .C. board (I/F) error.
• Resistance value of sensor is infinite
• IGBT built-in temp sensor error
→ Exchange IPDU P .C. board.
or zero (Open/Short).
Check item (position)