Toshiba Super MMU-AP0092H Service Manual page 54

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

No.
Item
6
Air speed
1) Operation with (HH), (H), (L) or [AUTO] mode is carried
selection
2) When the air speed mode [AUTO] is selected, the air
<COOL>
• Controlling operation in case when thermo of remote
• If the air speed has been changed once, it is not
• When cooling operation has started, select a down-
• If the temperature is just on the difference boundary,
<HEAT>
Value in the parentheses indicates one when thermostat
of the remote controller works.
Value without parentheses indicates one when thermo-
stat of the body works.
• If the air speed has been changed once, it is not
• When heating operation has started, select an upward
• If the temperature is just on the difference boundary,
• In Tc2 ≥ 60°C, the air speed increases by 1 step.
Outline of specifications
out by the command from the remote controller.
speed varies by the difference between Ta and Ts.
Ta (˚C)
+3.0
HH
+2.5
<HH>
+2.0
H+ <HH>
+1.5
H <HH>
+1.0
L+ <H+>
+0.5
L <H>
Tsc
L <H>
–0.5
L <L+>
< > : Indicate automatic cooling.
controller works is same as a case when thermo of
the body works.
changed for 3 minutes. However when the air volume
is exchanged, the air speed changes.
ward slope for the air speed, that is, the high position.
the air speed does not change.
Ta (˚C)
L <L+>
(–0.5) –1.0
L+ <H>
(0) Tsh
H <H+>
(+0.5) +1.0
H+
<HH>
(+1.0) +2.0
HH
(+1.5) +3.0
<HH>
(+2.0) +4.0
< > : Indicate automatic heating.
Body thermostat works.
Remote controller thermostat works.
changed for 1 minute. However when the air speed
exchanged, the air speed changes.
slope for the air speed, that is, the high position.
the air speed does not change.
A
B
C
D
E
F
G
E
D
C
B
A
54
Remarks
HH > H+ > H > L+ > L > UL
Code No. 32
0000: Body thermo. (Main unit)
0001: Remote controller
thermo.
Tc2: Indoor heat exchanger
sensor temperature

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents