Toshiba Super MMU-AP0092H Service Manual page 60

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

No.
Item
18
Louver contro
(Continued):
In case of
4-way Discharge
Cassette type
Outline of specifications
<<Selection of Swing mode>>
• For the Swing mode, the following three types of modes
are selectable and settable by keeping Swing/Direction
SWING/FIX
button pushed for 4 seconds or more on the remote
controller.
1) Standard (4 pieces: same phase) swing
→ Data: [0001 (At shipment)]
When Swing operation is selected, four louvers align at
the horizontal discharge position and then start the
Swing operation at the same time.
2) Dual swing → Data: [0002]
When operation is selected, the louvers of louver No.
[01] and [03] move to the horizontal discharge position,
the louvers of louver No. [02] and [04] move to the
downward discharge position and then start the Swing
operation at the same time.
3) Cycle swing → Data: [0003]
When operation is selected, the louver No. [01] moves to
the horizontal discharge position, [03] to the downward
discharge position, [02] and [04] to the middle position
and then start the Swing operation at the same time.
• Three types of the swing modes can be also selected
and set by the setup data of Item code (DN) [F0].
• In case of selecting the Swing mode, "Dual swing" or
"Cycle swing", the following numerals is displayed at
the center of the remote controller screen for approx.
SWING/FIX
3 seconds when
[SWING]. (No display for the standard swing)
Alternate lighting
(0.5 sec.)
Dual swing
<<Louver lock (Louver fix)>>
• For the air direction setup for each discharge port, the louver
position can be locked during the normal operation.
• An arbitrary air direction of an arbitrary louver can be
registered and set by keeping
4 seconds or more on the remote controller.
• The louver lock can be set by registering the setup data to
Item code (DN) [F1] to [F4] according to the following table.
Item code
Objective louver No.
F1
01
F2
02
F3
03
F4
04
button was pushed to select
Alternate lighting
(0.5 sec.)
Cycle swing
UNIT
LOUVER
button pushed for
Setup data
0000: Release (At shipment)
0001: Horizontal discharge position
~
0005: Downward discharge position
60
Remarks
On the remote controller
before the wired remote
controller (RBC-AMT32E),
the mode cannot be
moved to the select mode
SWING/FIX
even if pushing
button for a long time.
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.
The standard swing
performs the same swing
operation as the present
operation (2 series).
For the setting operation,
refer to [How to set up type
of the swings] in Item
"Setup at local site/
Others".
On the remote controller
before the wired remote
controller (RBC-AMT32E),
flashing showing the
Swing mode is not
indicated.
On the remote controller
before the wired remote
controller (RBC-AMT32E),
UNIT
LOUVER
button is not
provided.
Carry out setting operation
during stop of the unit;
otherwise the unit stops
operation.

Hide quick links: