Toshiba Super MMU-AP0092H Service Manual page 93

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

Lamp indication
Operation
Timer
Ready
Alternate flash
Operation
Timer
Ready
Alternate flash
Operation
Timer
Ready
Simultaneous flash
Operation
Timer
Ready
Flash
Operation
Timer
Ready
Simultaneous flash
Operation
Timer
Ready
Simultaneous flash
Operation
Timer
Ready
Simultaneous flash
Check code
F01
Heat exchanger sensor (TCJ) error
F02
Heat exchanger sensor (TC2) error
F03
Heat exchanger sensor (TC1) error
F10
Room temp. sensor (TA) error
F04
Discharge temp. sensor (TD1) error
F05
Discharge temp. sensor (TD2) error
F06
Heat exchanger sensor (TE1) error
F07
Liquid temp. sensor (TL) error
F08
Outside temp. sensor (TO) error
F12
Suction temp. sensor (TS1) error
F13
Heat sink sensor (TH) error
Misconnection of heat exchanger sensor (TE) with liquid temp. sensor (TL)
F15
→ Miswiring of temp. sensor in outdoor unit or miss-mounting
Miswiring between high pressure sensor (Pd) and low pressure sensor (Ps)
F16
→ Misconnection of pressure sensor in outdoor unit
F23
Low pressure sensor (Ps) error
F24
High pressure sensor (Pd) error
F29
Indoor unit EEPROM error
H01
Compressor break-down
H02
Compressor lock
H03
Current detection circuit error
H04
Compressor 1 case thermo operation
H06
Low pressure (Ps) drop error
H07
Oil face drop detection error
H08
Oil face detection circuit system temp. sensor (TK1, TK2, TK3, TK4) error
H14
Compressor 2 chase thermo operation: Protective device of outdoor unit operated.
H16
Oil face detection circuit system error: Outdoor unit TK1, TK2, TK3, TK4 circuit
system error
L03
Duplicated header units in indoor unit
L05
Duplicated priority indoor unit (Displayed in the room with priority)
L06
Duplicated priority indoor unit (Displayed in a room except one with priority)
L07
Group cable was connected to individual indoor unit.
L08
Indoor group address was unset.
L09
Indoor capacity was unset.
L04
Duplicated setting of outdoor line address
L10
Outdoor capacity was unset.
L17
Disagreement error of outdoor unit type
L18
COOL/HEAT select unit system error
L20
Duplicated address of central control system
L28
No. of connected outdoor units over
L29
Defective No. of IPDU
L30
Indoor unit outside interlock error
F31
Outdoor unit EEPROM error
Cause of trouble occurrence
Temp. sensor error in indoor unit
Outdoor unit temp. sensor error
Pressure sensor error in outdoor unit
Outdoor unit compressor system error
Protections stop of outdoor unit
93