Toshiba Super MMU-AP0092H Service Manual page 53

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

No.
Item
3
Room temp.
2) Using the Item code 06, the setup temperature in heating
control
(Continued)
4
Automatic
1) Based on the difference between Ta and Ts, the opera-
capacity control
5
Automatic
1) The judgment of selecting COOL/HEAT is carried out as
cooling/heating
control
2) For the automatic capacity control after judgment of
3) For temperature correction of room temp. control in
Outline of specifications
operation can be corrected.
Setup data
Setup temp. correction
Setting at shipment
Setup data
2
tion capacity is determined by the outdoor unit.
COOL
Ta
(˚C)
+2
SD
SB
+1
S9
S7
Ts
S5
S3
S0
–1
shown below. When +1.5 exceeds against Tsh
10 minutes and after thermo.-OFF, heating operation
(Thermo. OFF) exchanges to cooling operation.
Description in the parentheses shows an example of
cooling ON/OFF.
Ta
Cooling
(˚C)
+1.5
Tsc
or
Tsh
(Cooling OFF)
-1.5
When –1.5 lowers against Tsc 10 minutes and after
thermo. OFF, cooling operation (Thermo. OFF)
exchanges to heating operation.
cooling/heating, see Item 4.
automatic heating, see Item 3.
0
2
4
+0°C
+2°C
+4°C
+6°C
HEAT
Ta
(˚C)
+1
S3
S0
S5
Ts
S7
S9
–1
SB
SD
–2
SF
(Cooling ON)
Heating
53
Remarks
Shift of suction
temperature in heating
operation
6
Except while sensor of
the remote controller is
controlled
(Code No. [32], "0001")
Ts: Setup temp.
Ta: Room temp.
∗ For SHRM only
Tsc: Setup temp. in
cooling operation
Tsh: Setup temp. in
heating operation +
temp. correction of
room temp. control