Toshiba Super MMU-AP0092H Service Manual page 92

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

n Indoor unit display part (Receiving unit) (Wireless type)
When specifying the check code, check 7-segment display on the center unit.
For the check code which is not displayed on the outdoor 7-segment, confirm it in Section
"9-2 How to Check / Check code display list (Indoor unit)".
Lamp indication
Operation
Timer
Ready
No indication at all
Operation
Timer
Ready
Flash
Operation
Timer
Ready
Flash
Operation
Timer
Ready
Alternate flash
Operation
Timer
Ready
Alternate flash
Check code
Power supply OFF or miswiring between receiving unit and indoor unit
E01
Receiving error
E02
Sending error
E03
Communication interruption
E08
Duplicated indoor unit No. (Address)
E09
Duplicated header units of remote controller
E10
Communication error between MCU on indoor unit P.C. board
E12
Automatic address start error
E18
Wire connection error between indoor units, indoor power supply OFF
Miswiring or wire connection error between indoor unit and outdoor unit
E04
(Communication interruption between indoor and outdoor units)
Communication (receiving) error between indoor and outdoor units, decrease of
E06
No. of connected indoor units
E07
Communication (sending) error between indoor and outdoor units
E15
No indoor unit during setting of automatic address
E16
No. of connected indoor units, capacity over
E19
Error of No. of center unit
E20
Disagreement of refrigerant pipe communication during setting of automatic address
E23
Communication (sending) error between outdoor units
E25
Duplicated setting of follower unit address
Communication (receiving) error between outdoor units, decrease of No. of
E26
connected outdoor units
E28
Follower unit error
E31
IPDU communication error
P01
Indoor fan error
P10
Indoor overflow error
P12
Indoor fan error
P13
Outdoor unit liquid back detection error
P03
Outdoor unit discharge temp. (TD1) error
P04
Outdoor unit high pressure switch operation
P05
Outdoor unit open phase error was detected, negative phase error was detected
Outdoor unit heat sink overheat error: Heat radiation error of electric part (IGBT)
P07
in outdoor unit
P15
Gas leak was detected: Short of refrigerant charge amount
P17
Outdoor unit discharge temp. (TD2) error
P19
Outdoor unit 4-way valve inverse error
P20
High pressure protection error
P22
Outdoor unit DC fan error
P26
Outdoor unit G-Tr short-circuit error
P29
Compressor position detection circuit error
P31
Other indoor unit stopped due to error in the group.
: Goes off,
: Goes on,
Cause of trouble occurrence
Receiving unit
Miswiring or wire connection error
between receiving unit and indoor unit
92