Toshiba Super MMU-AP0092H Service Manual page 101

4-way air discharge cassette type
Hide thumbs Also See for Super MMU-AP0092H:
Table of Contents

Advertisement

Check code
Main
Outdoor 7-segment display
remote
controller
Check code
Auxiliary code
L05
L06
L06
No. of indoor units with priority
L07
L08
L08
L09
L10
L10
L17
L17
L18
L18
Corresponding indoor address
L20
L28
L28
L29
L29
01: IPDU1 error
02: IPDU2 error
03: IPDU1, 2 errors
04: Fan IPDU error
05: IPDU1 + Fan IPDU error
06: IPDU2 + Fan IPDU error
07: All IPDU error or communication error
between IPDU and I/F P .C. board, or
outdoor I/F P .C. board error
L30
L30
Detected indoor address
L31
Detected
Check code name
position
I/F
Duplicated indoor units with priority
(Displayed on indoor unit with priority)
I/F
Duplicated indoor units with priority
(Displayed on the unit other than
indoor unit with priority)
Indoor
Group line in individual indoor unit.
Indoor
Indoor group / address unset
Indoor
Indoor capacity unset
I/F
Outdoor capacity unset
I/F
Inconsistent models of outdoor units
I/F
FS unit system error
TCC-Link
Duplicated central control addresses
Indoor
I/F
Quantity over of connected outdoor
units
I/F
IPDU quantity error
Indoor
Interlock in indoor unit from outside
I/F
Extended IC (Integrated Circuit) error
Status
Error detection condition
All stop
Indoor units with priority were
duplicated.
All stop
Indoor units with priority were
duplicated.
Corresponding
At least one indoor unit connected
unit only stops.
to a group existed in the individual
indoor units.
Corresponding
Address was not yet set up.
unit only stops.
Corresponding
Indoor unit capacity was unset.
unit only stops.
All stop
On the I/F P .C. board for service,
jumper line was not cut according to
the model.
When outdoor unit models are
intermingled. When 1/2 series of
SHRM was intermingled.
Corresponding
An indoor unit which is not
unit only stops.
connected with FS unit is driving
without setup for cooling only mode.
All stop
Duplicated central control addresses
All stop
There were more than four outdoor
units.
All stop
No. of IPDU units detected when
power was turned on were less.
Corresponding
• Outside error input terminal
unit only stops.
Detected signal to (CN80) for
more 1 minute
Operation
P .C. board (I/F) parts error
continues.
Check item (position)
• Check display of indoor unit with priority.
• Check display of indoor unit with priority and
outdoor unit.
• Check indoor address.
• Check indoor address.
Note)
After installation, this code is displayed when the
power is firstly turned on.
Set up indoor capacity. (DN=11)
Check model setup on outdoor I/F P .C. board A'ssy
for service.
• Check outdoor units.
• Check setup of remote controller (DN=[OFF]).
• Check FS unit.
Check pipe connection to FS unit.
(Mispiping between discharge gas and suction gas)
Check miswiring/misinstallation of SVS/SVD valves.
• Check central control address.
• Check network adaptor P .C. board.
(In case of TCC-Link)
• Check No. of connected outdoor units.
(Max. 4 units per 1 system)
• Check communication line between outdoor units.
• Check outdoor P .C. board (I/F) error.
• Check model setup for outdoor I/F service P .C.
board.
• Check connection of UART communication
connector.
• Check IPDU, fan IPDU, and I/F P .C. board error.
Note)
UART: Universal Asynchronous Receiver Transmitter
n Outside device is connected to connector (CN80):
1) Check outside device error.
2) Check indoor P .C. board error.
n Outside device is not connected to connector (CN80):
1) Check indoor P .C. board error.
Check indoor (I/F) P .C. board.