Isolated Output Wiring Diagrams - Powerware 9170 User Manual

3kva-18kva, 50 and 60 hz
Hide thumbs Also See for 9170:
Table of Contents

Advertisement

C H A P T E R
I
O
SOLATED
The wiring diagrams in this section are unique and specific to
installations in which the output of the Powerware 9170 UPS is
galvanically isolated from the input.
Figure 37 through Figure 40 describe output wiring configurations for
various output voltages. Use Table 6 to find the desired wiring diagrams
and connect the output AC wiring to the proper Powerware 9170 system
power terminals. You must also set the operating menu parameter 7-3-4
for the required output voltage as shown in the wiring configuration
drawings.
Table 6. Wiring Diagrams for Isolated Output
UPS Input
UPS Input
UPS Output
UPS Output
Voltage
Voltage
100/200
100/200
110/220
110/220
115/230
115/230
115/230
115/230
120/240
120/240
120/208**
120/240
120/208**
120/208
120/208
120/208
127/220**
127/220
*Split-phase power modules required.
**External bypass switch, if installed, must be Break-Before-Make.
Powerware
9170 User's Guide
®
5
W
UTPUT
IRING
NOTE For isolated outputs, all power modules in the Powerware 9170 UPS cabinet
must be split-phase modules, which have blue labels.
NOTE In isolated-output installations, connect the UPS green and yellow
neutral-to-ground wire (N-G bond) to UPS output terminal as illustrated in Figure 36 on
page 45.
Output Wires
Output Wires
L1, L2, N*
L1 L2 N*
L1, L2, N*
L1 L2 N*
:
www.powerware.com
D
IAGRAMS
External
External
Bypass
Input
Yes
Figure 25a
No
Figure 25a
Yes
Figure 25a
Figure 25a
No
Wiring Diagrams
Output
System
Figure 34
Figure 37
Figure 34
Figure 38
Figure 35
Figure 39
Figure 35
Figure 40
43