Ups-Mounted Bypass Switch Installation; Maintenance Bypass/Power Distribution Module Setup - Powerware 9155 User Manual

8-15 kva
Hide thumbs Also See for 9155:
Table of Contents

Advertisement

Chapter 6

Maintenance Bypass/Power Distribution Module Setup

Powerware
9155 UPS (8–15 kVA) User's Guide
®

UPS-Mounted Bypass Switch Installation

This chapter describes the Maintenance Bypass Module and Power
Distribution Module installation. Both modules have a
Make-Before-Break Maintenance Bypass switch.
If you purchased an optional MBM/PDM, attach the module to the UPS
before any wiring installation. All hardware is supplied in the accessory
kit. Use the following procedure to attach the optional MBM/PDM to the
UPS:
1. Remove the connecting plate between the top cabinet and the
cabinet below it on the UPS rear panel (see Figure 13). Discard
the plate. Retain the screws for later use.
2. Remove the lowest top cover screw on each side of the UPS and
discard.
Lowest Top Cover
Screw (one each side)
Figure 13. UPS Rear View (2-High Cabinet Shown)
S
164201553 Rev D www.powerware.com
Connecting Plate
(8 screws)
29

Advertisement

Table of Contents
loading

Table of Contents