Setting The Input Type; Input Type - Omron E5CN User Manual

Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Setting the Input Type

3-2

Setting the Input Type

3-2-1

Input type

Operation Procedure
1,2,3...
Operation level
25
Initial setting level
Input type
20
The E5CN supports four input types: platinum resistance thermometer, ther-
mocouple, infrared temperature sensor and analog inputs. Set the input type
matched to the sensor used in the "input type" parameter. The E5CN specifi-
cations support two types of inputs, platinum resistance thermometer input
types and thermocouple input type, whose set values differ. Check the type of
E5CN at purchase.
Setting the input type "thermocouple K-20.0 to 500.0 ° C".
1. Press the
key for at least three seconds to move from the "operation
level" to the "initial setting level".
2. Press the
key to enter the set value of the desired sensor. When you
use K thermocouple (-20.0 to 500.0 ° C), enter "1" as the set value.
Hint:
The set value is fixed if you do not operate the keys on the front panel
for two seconds after changing the parameter, or by pressing the
or
keys.
List of Input Types
Input type
Platinum resis-
Platinum
tance ther-
resistance
mometer input
thermometer
type
Input type
Thermocouple
Thermocouple
input type
Infrared
temperature
sensor
ES1A
Analog input
Shaded ranges indicate default settings.
Name
Set
Input Temperature Setup Range
Value
-200 to 850 ( ° C)/ -300 to 1500 ( ° F)
Pt100
0
-199.9 to 500.0 ( ° C)/ -199.9 to 900.0 ( ° F)
1
0.0 to 100.0 ( ° C)/ 0.0 to 210.0 ( ° F)
2
-199.9 to 500.0 ( ° C)/ -199.9 to 900.0 ( ° F)
JPt100
3
0.0 to 100.0 ( ° C)/ 0.0 to 210.0 ( ° F)
4
Name
Set
Input Temperature Setup Range
Value
-200 to 1300 ( ° C)/ -300 to 2300 ( ° F)
K
0
-20.0 to 500.0 ( ° C)/ 0.0 to 900.0 ( ° F)
1
-100 to 850 ( ° C)/ -100 to 1500 ( ° F)
J
2
-20 to 400.0 ( ° C)/ 0.0 to 750.0 ( ° F)
3
-200 to 400 ( ° C)/ -300 to 700 ( ° F)
T
4
-199.9 to 400.0 ( ° C)/ -199.9 to 700.0 ( ° F)
17
0 to 600 ( ° C)/ 0 to 1100 ( ° F)
E
5
-100 to 850 ( ° C)/ -100 to 1500 ( ° F)
L
6
-200 to 400 ( ° C)/ -300 to 700 ( ° F)
U
7
-199.9 to 400.0 ( ° C)/ -199.9 to 700.0 ( ° F)
18
-200 to 1300 ( ° C)/ -300 to 2300 ( ° F)
N
8
0 to 1700 ( ° C)/ 0 to 3000 ( ° F)
R
9
0 to 1700 ( ° C)/ 0 to 3000 ( ° F)
S
10
100 to 1800 ( ° C)/ 300 to 3200 ( ° F)
B
11
10 to 70 ° C
0 to 90 ( ° C)/ 0 to 190 ( ° F)
12
60 to 120 ° C
0 to 120 ( ° C)/ 0 to 240 ( ° F)
13
115 to 165 ° C
0 to 165 ( ° C)/ 0 to 320 ( ° F)
14
160 to 260 ° C
0 to 260 ( ° C)/ 0 to 500 ( ° F)
15
0 to 50mV
16
One of the following ranges depending on the
results of scaling:
-1999 to 9999, -199.9 to 999.9,
-19.99 to 99.99, -1.999 to 9.999
Section 3-2