Setting the Input Type

3-2

Setting the Input Type

3-2-1

Input Type

Operating Procedure
Operation Level
C
25.0
0.0
Initial Setting Level
Input Type
in-t
5
in-t
6
List of Input Types
Input type
Specifications
Platinum resistance
Pt100
thermometer
JPt100
Thermocouple
K
J
T
E
L
U
N
R
S
B
W
PLII
K
J
T
52
The Controller supports 3 input types: platinum resistance thermometer, ther-
mocouple, and analog inputs. Set the input type that matches the sensor that
is used.
The following example shows how to set a K thermocouple for
500.0 C.
1. Press the O Key for at least three seconds to move from the operation
level to the initial setting level.
2. Press the U Key to enter the set value of the desired sensor.
When you use a K thermocouple ( 20.0 to 500.0 C), enter 6 as the set
value.
Hint: The key operation is saved two seconds after the change, or by press-
ing the O or M Key.
Set value
0
200.0 to 850.0 ( C)/ 300.0 to 1,500.0 ( F)
1
199.9 to 500.0 ( C)/ 199.9 to 900.0 ( F)
2
0.0 to 100.0 ( C)/0.0 to 210.0 ( F)
3
199.9 to 500.0 ( C)/ 199.9 to 900.0 ( F)
4
0.0 to 100.0 ( C)/0.0 to 210.0 ( F)
5
200.0 to 1,300.0 ( C)/ 300.0 to 2,300.0 ( F)
6
20.0 to 500.0 ( C)/0.0 to 900.0 ( F)
7
100.0 to 850.0 ( C)/ 100.0 to 1,500.0 ( F)
8
20.0 to 400.0 ( C)/0.0 to 750.0 ( F)
9
200.0 to 400.0 ( C)/ 300.0 to 700.0 ( F)
10
199.9 to 400.0 ( C)/ 199.9 to 700.0 ( F)
11
200.0 to 600.0 ( C)/ 300.0 to 1,100.0 ( F)
12
100.0 to 850.0 ( C)/ 100.0 to 1,500.0 ( F)
13
200.0 to 400.0 ( C)/ 300.0 to 700.0 ( F)
14
199.9 to 400.0 ( C)/ 199.9 to 700.0 ( F)
15
200.0 to 1,300.0 ( C)/ 300.0 to 2,300.0 ( F)
16
0.0 to 1,700.0 ( C)/0.0 to 3,000.0 ( F)
17
0.0 to 1,700.0 ( C)/0.0 to 3,000.0 ( F)
18
100.0 to 1,800.0 ( C)/300.0 to 3,200.0 ( F)
19
0.0 to 2,300.0 ( C)/0.0 to 3,200.0 ( F)
20
0.0 to 1,300.0 ( C)/0.0 to 2,300.0 ( F)
21
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
22
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
23
50.0 to 200.0 ( C)/ 50.0 to 200.0 ( F)
Input temperature setting range