Parameter Structure
6-1
Parameter Structure
Advanced function
setting level
108
• To calibrate the E5CN, enter the password "1201" at the "move to calibra-
tion level" parameter in the "advanced function setting level". "adj" is dis-
played.
• However, note that the "move to calibration level" parameter might not be
displayed when, for example, the user is calibrating the E5CN for the first
time. If this happens, set the "initial/communications protection" parame-
ter in the protect level to "0" before moving to the "advanced function set-
ting level".
• The parameters in the calibration level are structured as follows:
These parameters are automatically moved to according to the event input.
Once the user has calibrated the E5CN, a dot will be displayed when the cali-
bration level is moved to, to indicate that the E5CN has already been cali-
brated by the user.
Dot is displayed.
Section 6-1