Omron E5CN User Manual page 10

Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Safety Precautions
xiv
3. To reduce induction noise, separate the high-voltage or large-current pow-
er lines from other lines, and avoid parallel or common wiring with the pow-
er lines when you are wiring to the terminals. We recommend using
separating pipes, ducts, or shielded lines.
4. Do not use this product in the following places:
• Places subject to dust or corrosive gases (in particular, sulfide gas and
ammonia gas)
• Places subject to high humidity, condensation or freezing
• Places subject to direct sunlight
• Places subject to vibration and large shocks
• Places subject to splashing liquid or oily atmosphere
• Places directly subject to heat radiated from heating equipment
• Places subject to intense temperature changes
5. To allow heat to escape, do not block the area around the product. (Ensure
that enough space is left for the heat to escape.)
• Do not block the ventilation holes on the casing.
6. When you draw out the internal mechanism from the housing, never touch
electric components inside or subject the internal mechanism to shock.
7. Cleaning: Do not use paint thinner or the equivalent. Use standard grade
alcohol to clean the product.
8. Use specified size (M3.5, width 7.2 mm or less) crimped terminals for wir-
ing.
9. Allow as much space as possible between the E5CN and devices that gen-
erate powerful high-frequency noise (e.g. high-frequency welders, high-
frequency sewing machines) or surges.
10. When executing self-tuning, turn the load (e.g. heater) ON simultaneously
or before you turn the E5CN ON. If you turn the E5CN ON before turning
the load ON, correct self-tuning results and optimum control may no longer
be obtained.
11. Use a 100 to 240 VAC (50/60 Hz), 24 VAC (50/60 Hz) or 24 VDC power
supply matched to the power specifications of the E5CN. Also, make sure
that rated voltage is attained within two seconds of turning the power ON.
12. Attach a surge suppresser or noise filter to peripheral devices that gener-
ate noise (in particular, motors, transformers, solenoids, magnetic coils or
other equipment that have an inductance component).
13. When mounting a noise filter on the power supply, be sure to first check the
filter's voltage and current capacity, and then mount the filter as close as
possible to the E5CN.
14. Use within the following temperature and humidity ranges:
• Temperature: -10 to 55 ° C, Humidity: 25 to 85% (with no icing or conden-
sation)
If the E5CN is installed inside a control board, the ambient temperature
must be kept to under 55 ° C, including the temperature around the E5CN.
If the E5CN is subjected to heat radiation, use a fan to cool the surface of
the E5CN to under 55 ° C.
15. Store within the following temperature and humidity ranges:
• Temperature: -25 to 65 ° C, Humidity: 25 to 85% (with no icing or conden-
sation)
16. Never place heavy objects on, or apply pressure to the E5CN as it may
cause it to deform and deteriorate during use or storage.
17. Avoid using the E5CN in places near a radio, television set, or wireless in-
stallation. These devices can cause radio disturbances which adversely af-
fect the performance of the E5CN.
3

Hide quick links:

Advertisement

Table of Contents
loading