Advanced Function Setting Level
hbu
HBA used
Function
Setting
hbl
Heater burnout latch
Function
Setting
See
hbh
Heater burnout hysteresis
Function
Setting
See
• This parameter sets use of the heater burnout alarm.
Setting Range
;:: Enabled / ;22: Disabled
• When this parameter is set to ON, the heater burnout alarm is held until
either of the following conditions is satisfied: Output is turned OFF when
the initial setting level, communications setting level, advanced function
setting level or calibration level is switched to.
a
Heater burnout detection is set to "0.0A".
b
The power is turned OFF then back ON again (power is reset).
Setting Range
;:: Enabled / ;22: Disabled
Related parameters
"HBA used" (advanced function setting level)
• This parameter sets the hysteresis when HBA is detected.
Setting Range
0.1 to 50.0
Related parameters
"HBA used" (advanced function setting level)
The option event input unit E53-
CNHB or the communication unit
E53-CNH03 must be mounted in the
E5CN.
Default
;:
The "HBA used" parameter must be
set to "ON".
Default
;22
The "heater burnout latch" parameter
must be set to OFF.
Unit
Default
A
0.1
Section 5-6
95