User Calibration - Omron E5CN User Manual

Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

User Calibration

6-2

User Calibration

Calibrating input
Registering calibration
data
The E5CN is correctly calibrated before it is shipped from the factory, and nor-
mally need not be calibrated by the user.
If, however, it must be calibrated by the user, use the parameters for calibrat-
ing temperature input and analog input.
However, note that OMRON cannot ensure the results of calibration by
the user.
Also, calibration data is overwritten with the latest settings. The default
calibration settings cannot be returned to after user calibration.
When the user calibrates the E5CN, the input type currently selected in
parameters is calibrated. The following 22 input types can be calibrated.
• Thermocouple :
• Infrared temperature sensor :
• Analog input :
• Platinum resistance thermometer : 5 types
The new calibration data for each item is temporarily registered. It can be offi-
cially registered as calibration data only when all items have been calibrated
to new values. So, be sure to temporarily register all items when you calibrate
the E5CN.
When calibration data is registered, it is registered regardless of whether or
not the E5CN has been calibrated by the user.
Prepare separate measuring devices and equipment for calibration. For
details on how to handle measuring devices and equipment, refer to the
respective instruction manuals.
12 types
4 type
1 type
Section 6-2
109