Determining PID Constants (AT, ST, manual setup)

3-8

Determining PID Constants (AT, ST, manual setup)

3-8-1

AT (auto-tuning)

Description
28
• When you execute auto-tuning, the optimum PID constants for the set
point during program execution are automatically set by forcibly changing
the manipulated variable to calculate the characteristics (called the "limit
cycle method") of the control target.
• To execute AT (auto-tuning), specify "on: AT execute", and to cancel AT
(auto-tuning), specify "off: AT cancel".
• AT (auto-tuning) cannot be executed during ON/OFF control.
• The result of AT (auto-tuning) is mirrored in the "proportional band (P),"
"integral time (I)" and "derivative time (D)" parameters in the "adjustment
level".
Adjustment level
Proportional band
Integral time
Derivative time
AT (auto-tuning) is started when the "AT execute/cancel" parameter is set to
"ON". During execution of AT, the No.1 display for the "AT execute/cancel"
parameter blinks. When AT ends, the "AT execute/cancel" parameter turns
OFF, and the No.1 display stops blinking.
AT execute/cancel
If you move to the "operation level" during AT execution, the No.2 display
blinks to indicate that AT is being executed.
PV/SP
Only the "communications writing", "run/stop" and "AT execution/cancel"
parameters can be changed during AT execution. Other parameters cannot
be changed.
Section 3-8
No.1 display
During AT execution
No.2 display
During AT execution