Omron E5CN User Manual page 93

Hide thumbs Also See for E5CN:
Table of Contents

Advertisement

Initial Setting Level
PID / ON/OFF
Function
Setting
See
Standard/heating and
s-hc
cooling
Function
Setting
See
• This parameter selects 2-PID control or ON/OFF control.
• The AT and ST tuning functions can be used in 2-PID control.
Setting Range
<50: 2-PID /;:;2: ON/OFF
Related parameters
"AT execute/cancel" "Manual reset" "Hysteresis (OUT1)" "Hysteresis (OUT2)"
(adjustment level)
"ST stable range" (advanced function setting level)
• This parameter selects standard control or heating and cooling control.
• When heating and cooling control is selected, the alarm 2 output terminal
"ALM2" is used for control output 2 side output. So, alarm 2 cannot be
used.
Setting Range
?@:0: Standard /4/: Heating and cooling
Related parameters
"MV monitor (OUT1)" "MV monitor (OUT2)" (operation level)
"Alarm value 1" "Upper-limit alarm value 1" "Lower-limit alarm value 1" (opera-
tion level)
"Hysteresis (OUT2)" "Cooling coefficient" "Dead band" (adjustment level)
"Control period (OUT2)" (initial setting level)
"Alarm 1 type" (initial setting level)
"Alarm 1 hysteresis" "Alarm 1 open in alarm" (advanced function setting level)
Section 5-5
Default
;:;2
The E5CN must support alarm 2 out-
put.
Default
?@:0
83